Reference

Roof Pitch Calculator for the UK and NZ: Degrees, Tiles and Falls

Reviewed by the My Roof Pitch editorial team · Updated

In the UK and New Zealand, roof pitch is expressed in degrees from horizontal, not as a rise-over-run ratio. Minimum pitch depends on the covering: concrete/clay tiles typically need 15–22.5°, natural slate 20–25°, and single-ply or felt flat roofs need at least a 1:40 fall (about 1.4°) to shed water, per BS 5534 and NZ E2/AS1.

Key takeaways

  • UK and NZ roofers measure pitch in degrees from horizontal, unlike the US inches-per-12-inches convention.
  • Minimum tile pitch is typically 15–22.5° for concrete/clay interlocking tiles and 20–25° for natural slate, set by manufacturer data sheets and BS 5534 in the UK.
  • In New Zealand, roof pitch and weathertightness are governed by NZBC Clause E2 and the E2/AS1 acceptable solution, with product-specific minimums from manufacturers like Gerard, Metrotile and Dimond.
  • Pent (single-slope) roofs commonly run 5–15°; below about 5° they are treated as flat roofs needing a membrane and a minimum 1:40 fall.
  • Metric pitch is calculated the same way as imperial — angle = arctan(rise ÷ run) — just measured in millimetres or metres instead of inches.
  • Flat roof fall is expressed as a ratio (e.g. 1:40) or in mm per metre, not in degrees, because the angle is too shallow to read meaningfully.

Why the UK and NZ use degrees, not x-in-12

The American rise-over-run convention (e.g. '6 in 12', meaning 6 inches of rise per 12 inches of run) is rare in the UK and New Zealand trade. Both countries use metric measurements and express roof pitch as an angle in degrees from horizontal, matching the way building regulations, manufacturer technical data sheets and structural calculations are written. A '30 degree roof' or 'pitched at 35°' is the standard way to describe a roof on a UK or NZ building consent or tile manufacturer's datasheet.

This matters practically because tile, slate and membrane manufacturers publish minimum pitch requirements strictly in degrees. Converting an imperial rise-over-run figure (common in older pattern books or imported literature) into degrees is often the first step before checking it against UK or NZ compliance tables.

Pitch conversion: degrees, ratio and percentage

Common roof pitches in degrees with equivalent ratio and percentage fall
DegreesRise:Run (approx.)Percentage gradeTypical use
1.4°1:402.5%Minimum flat roof membrane fall
5°1:11.48.7%Minimum pent/mono-pitch, standing seam metal
10°1:5.717.6%Low-pitch tiled roof (manufacturer-dependent)
15°1:3.726.8%Minimum pitch for many interlocking concrete tiles
22.5°1:2.441.4%Common minimum for plain/clay tiles
30°1:1.7357.7%Standard UK/NZ residential pitch
35°1:1.4370.0%Common slate roof pitch
45°1:1100%Steep traditional pitch, attic conversions
Common roof pitches in degrees with equivalent ratio and percentage fall

Note the percentage grade column is not the same as the degree value — they diverge quickly above 20°, which trips up anyone assuming 'percent' and 'degrees' are interchangeable. Always check which unit a spec sheet or building control officer is asking for before quoting a number.

UK minimum pitch for tiles and slate (BS 5534)

In the UK, BS 5534 (the code of practice for slating and tiling) sets the framework for wind uplift and exposure-based fixing specifications, but the actual minimum pitch for a given product comes from that manufacturer's BS 5534-compliant test data, cross-checked against exposure zone, rafter length and the underlay type used. As a general guide across common UK products:

Typical UK minimum roof pitch by covering
CoveringTypical minimum pitchNotes
Interlocking concrete tile15°–17.5°Varies by profile; some low-pitch ranges go to 12.5°
Plain clay tile (double-lap)35°–40°Steeper due to smaller unit overlap
Natural slate20°–25°Depends on slate size and head lap per BS 5534
Fibre cement slate15°–20°Manufacturer-specific, check NHBC/BBA certificate
Standing seam metal1°–5°Sealed seams allow near-flat use
Profiled steel/fibre cement sheet4°–10°Minimum lap and fixing specified by manufacturer
Felt/single-ply flat roof membraneMin. 1:40 fall (~1.4°)BS 6229 for flat roof design
Typical UK minimum roof pitch by covering

NZ minimum pitch and weathertightness (E2/AS1)

New Zealand ties roof pitch to weathertightness performance under the New Zealand Building Code Clause E2 (External Moisture), with E2/AS1 as the most commonly used acceptable solution for residential roofing. E2/AS1 sets minimum pitches for roofing types based on the roof cladding, the length of the roof plane, and the exposure (wind zone) of the site — steeper pitch or shorter roof planes are required in higher wind zones.

Typical NZ minimum roof pitch guidance under E2/AS1
Roof claddingTypical minimum pitchNotes
Corrugated steel (long run)3°–8°Shorter roof planes can go lower; check product MOP
Trapezoidal steel profile1.5°–3°Low-pitch capable profiles like Trimdek/Dimondek
Concrete/clay tile17.5°–25°Varies by manufacturer (Monier, Gerard, Terreal)
Metal tile (e.g. Gerard, Metrotile)8°–12.5°Pressed metal profile allows lower pitch than clay
Membrane (torch-on/single-ply)Min 1:40–1:60 fallTreated as a flat roof; needs engineered falls to outlets
Typical NZ minimum roof pitch guidance under E2/AS1

Because New Zealand has strong regional wind zone variation — from 'low' to 'extra high' under NZS 3604 — the same roofing product can have a different minimum pitch in Wellington than in Auckland. Always check the manufacturer's published Appraisal or BRANZ technical statement for the specific wind zone before finalising a design, as this is what building consent authorities will check against.

Pent roof pitch and mono-pitch design

A 'pent roof' (also called a mono-pitch or skillion roof) is a single sloped surface with no ridge, common on extensions, garages, sheds and increasingly on contemporary UK and NZ new-builds. Pent roofs typically run shallower than dual-pitch roofs — commonly 5° to 15° — because a single long slope at a steep angle would be structurally awkward and visually heavy on a small extension.

  • Below about 5°, a pent roof is functionally a flat roof and should be detailed with a waterproof membrane rather than tiles or slates.
  • Between 5° and 10°, standing seam metal, well-lapped corrugated sheet, or certain low-pitch tile systems can work, but check the manufacturer's minimum pitch carefully.
  • Above 10°, most standard tile, slate and sheet products become viable, subject to the exposure checks above.
  • Pent roof drainage usually runs to a single gutter along the low eave — size that gutter for the full roof catchment area, not half as on a dual-pitch roof.

A common design mistake is specifying a pent roof pitch purely for aesthetics (e.g. a very shallow 3° 'modern' look) without checking the chosen covering's certified minimum — this is one of the most frequent building control rejections on UK and NZ extensions.

Flat roof fall: ratios instead of degrees

Once a roof drops below roughly 5°, the angle becomes too shallow to describe usefully in degrees, so UK and NZ practice (and BS 6229 in the UK) switches to describing it as a 'fall' — a ratio or a rate of fall expressed in millimetres per metre.

Flat roof fall conversions
Fall ratiomm per metreApprox. degreesTypical application
1:4025 mm/m1.4°Minimum design fall, membrane roofs (BS 6229)
1:6016.7 mm/m0.95°Minimum as-built fall allowing for tolerance (design at 1:40)
1:8012.5 mm/m0.7°Below recommended minimum — ponding risk
1:2050 mm/m2.9°Generous fall, good drainage margin
Flat roof fall conversions

The key design rule in both countries: specify the fall steeper than the bare minimum, because construction tolerances, deck deflection and insulation settlement typically remove some of the designed fall over time. A roof designed exactly to 1:40 often performs closer to 1:60 once built, which is why BS 6229 recommends designing to 1:40 as the minimum, not the target.

Run the numbers

Frequently asked questions

How do I convert roof pitch from inches-per-foot to degrees for a UK or NZ job?

Divide the rise by the run to get a ratio, then take the arctangent of that ratio. For example, a 6:12 American pitch is 6 ÷ 12 = 0.5, and arctan(0.5) = 26.57°, which is how you'd specify it on a UK or NZ drawing or building consent.

What is the minimum roof pitch for concrete tiles in the UK?

Most interlocking concrete tile ranges have a certified minimum pitch of 15° to 17.5°, though this depends on the specific manufacturer's BS 5534 test data, the wind exposure zone, and the rafter length. Always check the product's technical data sheet rather than assuming a single universal figure.

What is the minimum roof pitch in New Zealand under E2/AS1?

It varies by cladding type and wind zone: corrugated steel can go as low as 3°, trapezoidal steel profiles as low as 1.5°, and concrete or clay tiles typically need 17.5° to 25°. E2/AS1 and the manufacturer's BRANZ appraisal set the exact figure for a given site's wind zone.

What pitch should a pent (mono-pitch) roof be?

Most pent roofs run between 5° and 15°. Below 5° they should be treated and detailed as a flat roof with a waterproof membrane rather than a tiled or sheeted pitched covering.

What is a 1:40 fall in degrees?

A 1:40 fall is approximately 1.4 degrees from horizontal. It is the minimum design fall recommended by BS 6229 for flat roof membranes in the UK, expressed as a ratio rather than degrees because the angle is too shallow to read meaningfully on site.

Is a steeper roof pitch always better for rain and wind in the UK and NZ?

Not necessarily. Steeper pitches shed water and snow faster and reduce wind uplift risk in some configurations, but they also increase wind loading on the roof plane, cost more in material and labour, and may hit height restrictions under local planning rules — the right pitch balances all of these, not just rainfall.

Do I need a different minimum pitch depending on roof plane length?

Yes, in both BS 5534 and NZ E2/AS1. Longer roof planes require steeper minimum pitches because water travels further across the surface before reaching a gutter, increasing the risk of wind-driven water penetrating laps — this is set out in the manufacturer's pitch/length tables.

Keep reading

Last updated 2026-10-08. Guidance is general information for planning and is not a substitute for a licensed engineer or local code review.